Prototype 1: Voltage follower and anti-alias filter

prototype1.JPG

Emon1CT Firmware:

  • Voltage follower on PA6 & PA7 for bias buffer (note: HAL_OPAMP_Start(&hopamp2); required)
  • Implements @Robert.Wall's offset removal technique

Emon3CT Firmware:

  • Extension of the 1CT example to 3 CT inputs.

Anti-alias filter based on:

antialias.png

Two 1k resistors + 22pF capacitors to ground, biased with output from voltage follower.

40W incandescent lightbulb:

Vrms    Irms    RP      AP      PF      Count
239.86  0.184   43.8    44.1    0.995   287122
239.85  0.183   43.8    43.9    0.998   289544
239.94  0.184   43.9    44.1    0.995   289507
240.07  0.183   43.9    43.9    0.999   287142
240.12  0.184   43.9    44.1    0.996   289462
239.98  0.184   43.9    44.1    0.995   282377
239.76  0.184   43.8    44.0    0.995   284698

Electric room heater:

229.96  7.908   1816.4  1818.5  0.999   289401
229.84  7.901   1813.9  1816.0  0.999   291787
229.83  7.900   1813.5  1815.6  0.999   289468
230.05  7.907   1816.9  1819.0  0.999   289500
230.07  7.907   1817.2  1819.2  0.999   287145
230.05  7.906   1816.7  1818.8  0.999   291873

Laptop:

239.41  0.134   17.1    32.0    0.535   287153
239.48  0.139   17.9    33.2    0.540   284790
239.58  0.140   18.1    33.4    0.542   291839
239.62  0.144   18.8    34.5    0.544   287131
239.50  0.132   17.0    31.6    0.538   289426
239.45  0.136   17.6    32.5    0.541   291730

Readings are printed every ~2.5 seconds (125 cycles 50Hz), ~287122 VI sample pairs every 2.5s = 115 kHz

22pF filter cap on CT input:

22pfCT.png

100nF filter cap on CT input:

100pfCT.png

No filter cap on CT input:

nocapCT.png

100nF filter cap on Voltage input (22pF on other screenshots), showing to low cut off frequency:

100pfV.png